Por favor, use este identificador para citar o enlazar este ítem: http://hdl.handle.net/20.500.14076/26747
Registro completo de metadatos
Campo DC Valor Lengua/Idioma
dc.contributor.advisorTaipe Rojas, Javier Enrique-
dc.contributor.authorBustinza Orosco, Fernando Jesús-
dc.creatorBustinza Orosco, Fernando Jesús-
dc.date.accessioned2023-12-04T21:59:07Z-
dc.date.available2023-12-04T21:59:07Z-
dc.date.issued2023-
dc.identifier.urihttp://hdl.handle.net/20.500.14076/26747-
dc.description.abstractLa presente tesis realiza el análisis de riesgo de incendio en un establecimiento de salud, aplicando la metodología Fire Risk Assessment Method for Engineering - FRAME. Se utilizó el software de Excel que contiene las operaciones de la metodología FRAME, para calcular los diferentes niveles de riesgo, para finalmente calcular el riesgo inicial de incendio "Ro” y el nivel de riesgo de incendio de los diferentes niveles de piso del establecimiento de salud. El establecimiento de salud es una infraestructura compleja; ya que cuenta con diferentes áreas de atención, donde brinda asistencia médica, partos hasta el internamiento de personas. Esto implica que la infraestructura debe contar con el equipamiento adecuado para prevenir y controlar un incendio, con la finalidad de garantizar un sitio seguro para las personas y mantener la continuidad de los servicios de atención médica para los pacientes. El riesgo inicial de incendio, es menor a 1; mientras que el riesgo de patrimonio y/o bienes, para el tercer y cuarto piso, es mayor a 1; el riesgo para las personas, en todos los niveles de piso, es menor a 1; y el riesgo para las actividades, en todos los niveles de piso, es mayor a 1. El nivel de riesgo para el patrimonio y/o bienes, riesgo para las personas, y riesgo para las actividades; es mayor en el cuarto piso. Por ello, se tomará como nivel de referencia con respecto a los otros niveles de pisos, para poder implementar medidas de prevención y control de incendio adecuado y efectivo. Se identifica que en los diferentes niveles de pisos existen áreas críticas que no cuenta con un sistema adecuado para prevenir y controlar un incendio, como es un sistema de rociadores, sistema automático especial, falta de hidrantes, falta de plan de contingencia, entre otros. Como también la poca capacidad de almacenamiento de agua contraincendios que cuenta el establecimiento de salud. Asimismo, el establecimiento de salud cuenta en todos sus niveles de pisos con extintores manuales para las diferentes clases de fuego, sistema automático de detección, con distribución de gabinetes contraincendios. Sus infraestructuras cuentan con resistencia al fuego.es
dc.description.abstractThis thesis analyzes the risk of fire in a health establishment, applying the Fire Risk Assessment Method for Engineering - FRAME methodology. Using the Excel software that contains the operations of the FRAME methodology, to calculate the different risk levels, to finally calculate the initial fire risk "Ro" and the fire risk level of the different floor levels of the health facility. The health establishment is a complex infrastructure, since it has different care areas, where it provides medical assistance, childbirth to the hospitalization of people. That is why the infrastructure must have adequate equipment to prevent and control a fire. In order to guarantee a safe place for people and maintain the continuity of health care services for patients. The initial fire risk is less than 1; while the risk of equity and/or assets, for the third and fourth floors, is greater than 1; the risk to people, at all floor levels, is less than 1; and risk to activities. at all floor levels, it is greater than 1. The level of risk for assets and/or assets, risk for people, and risk for activities; it is higher on the fourth floor. That is why it will be taken as a reference level with respect to the other floor levels, in order to implement adequate and effective fire prevention and control measures. It is identified that in the different floor levels there are critical areas that do not have an adequate system to prevent and control a fire, such as a sprinkler system, special automatic system, lack of hydrants, lack of contingency plan, among others. As well as the low capacity for fire-fighting water storage that the health facility has. Likewise, the health establishment has manual fire extinguishers for the different classes of fire, an automatic detection system, and distribution of fire cabinets at all floor levels. Its infrastructures have fire resistance.en
dc.description.uriTesises
dc.formatapplication/pdfes
dc.language.isospaes
dc.publisherUniversidad Nacional de Ingenieríaes
dc.rightsinfo:eu-repo/semantics/restrictedAccesses
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/es
dc.sourceUniversidad Nacional de Ingenieríaes
dc.sourceRepositorio Institucional - UNIes
dc.subjectAnálisis de riesgo de incendioes
dc.subjectEstablecimiento de saludes
dc.subjectMétodo FRAMEes
dc.titleAnálisis de riesgo de incendio en establecimiento de saludes
dc.typeinfo:eu-repo/semantics/bachelorThesises
thesis.degree.nameIngeniero de Higiene y Seguridad Industriales
thesis.degree.grantorUniversidad Nacional de Ingeniería. Facultad de Ingeniería Ambientales
thesis.degree.levelTítulo Profesionales
thesis.degree.disciplineIngeniería de Higiene y Seguridad Industriales
thesis.degree.programIngenieríaes
renati.advisor.orcidhttps://orcid.org/0000-0002-9488-5836es
renati.author.dni46903995-
renati.advisor.dni10343176-
renati.typehttp://purl.org/pe-repo/renati/type#tesises
renati.levelhttp://purl.org/pe-repo/renati/nivel#tituloProfesionales
renati.discipline022016-
renati.jurorVillena Chávez, Jorge Alberto-
renati.jurorRobles García, Eusebio-
dc.publisher.countryPEes
dc.subject.ocdehttp://purl.org/pe-repo/ocde/ford#2.11.02es
Aparece en las colecciones: Ingeniería de Higiene y Seguridad Industrial

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
bustinza_of.pdf8,47 MBAdobe PDFVisualizar/Abrir
bustinza_of(acta).pdf431,38 kBAdobe PDFVisualizar/Abrir
informe_de_similitud.pdf430,65 kBAdobe PDFVisualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons

Indexado por:
Indexado por Scholar Google LaReferencia Concytec BASE renati ROAR ALICIA RepoLatin UNI