Por favor, use este identificador para citar o enlazar este ítem:
http://hdl.handle.net/20.500.14076/26931
Registro completo de metadatos
Campo DC | Valor | Lengua/Idioma |
---|---|---|
dc.contributor.advisor | Bautista Ríos, Juan Pablo | - |
dc.contributor.author | Pastor Escobar, Juan Jesús | - |
dc.creator | Pastor Escobar, Juan Jesús | - |
dc.date.accessioned | 2024-02-28T23:06:50Z | - |
dc.date.available | 2024-02-28T23:06:50Z | - |
dc.date.issued | 2023 | - |
dc.identifier.uri | http://hdl.handle.net/20.500.14076/26931 | - |
dc.description.abstract | El procedimiento para el dimensionamiento del cruce de líneas inicia con la simulación de la línea de transmisión existente L-5033 Poroma – Yarabamba de 500 kV, entre las estructuras E-585 y E-587, considerando las condiciones más críticas de operación se especifica las distancias hacia la línea de transmisión proyectada Solimana - Ocoña de 220 kV, es decir, entre los conductores y cables de guarda que cruzarán por debajo de los existentes. Es importante resaltar que la topografía en la zona de cruce presenta desniveles en dirección transversal y longitudinal. A continuación, se evalúa los efectos electromagnéticos en los puntos críticos en común de ambas líneas de transmisión sobre el terreno, tomando en cuenta diversas secuencias de fase en la línea proyectada para mostrar la influencia de su selección. Como resultado, el principal efecto electromagnético es el campo eléctrico, ya que influye directamente en la separación vertical entre conductores y al terreno, este efecto es sensible debido a la superposición de campos producido en conjunto con la línea de trasmisión existente de 500 kV. Adicionalmente, se evalúan las tensiones inducidas cuando la línea de 220 kV se encuentra desenergizada y se demuestra la influencia del ángulo de cruce. En resumen, el campo eléctrico producido en los puntos de intersección de servidumbres, en la zona de cruce, define la secuencia de fases de la línea proyectada. En consecuencia, el resto de la línea debe obedecer a dicha restricción. | es |
dc.description.abstract | The procedure for sizing the crossing of transmission lines begins with the simulation of the existing 500 kV transmission line L-5033 Poroma - Yarabamba, between structures E-585 and E-587, considering the most critical operating conditions. The distances to the projected 220 kV transmission line Solimana - Ocoña are specified, i.e., between the conductors and guard cables that will pass underneath the existing line. It is important to highlight that the topography in the crossing area presents elevation differences in both transversal and longitudinal directions. Then, the electromagnetic effects at the common critical points of both transmission lines on the ground are evaluated, considering various phase sequences in the projected line to show the influence of their selection. As a result, the main electromagnetic effect is the electric field since it directly affects the vertical separation between conductors and the ground. This effect is sensitive due to the superposition of fields produced in conjunction with the existing 500 kV transmission line. Additionally, induced voltages are evaluated when the 220 kV line is de-energized, and the influence of the crossing angle is demonstrated. In summary, the electric field generated at the intersection points of rights-of-way in the crossing area defines the phase sequence of the projected line. Consequently, the rest of the line must adhere to this restriction. | en |
dc.description.uri | Tesis | es |
dc.format | application/pdf | es |
dc.language.iso | spa | es |
dc.publisher | Universidad Nacional de Ingeniería | es |
dc.rights | info:eu-repo/semantics/openAccess | es |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | es |
dc.source | Universidad Nacional de Ingeniería | es |
dc.source | Repositorio Institucional - UNI | es |
dc.subject | Efectos electromagnéticos | es |
dc.subject | Cruce de líneas de transmisión | es |
dc.subject | Tensiones inducidas | es |
dc.subject | Secuencia de fases | es |
dc.subject | Ángulo de cruce de líneas | es |
dc.title | Análisis de los efectos electromagnéticos para el dimensionamiento del cruce de líneas de transmisión de 220 Kv y 500 Kv | es |
dc.type | info:eu-repo/semantics/bachelorThesis | es |
thesis.degree.name | Ingeniero Electricista | es |
thesis.degree.grantor | Universidad Nacional de Ingeniería. Facultad de Ingeniería Eléctrica y Electrónica | es |
thesis.degree.level | Título Profesional | es |
thesis.degree.discipline | Ingeniería Eléctrica | es |
thesis.degree.program | Ingeniería | es |
renati.advisor.orcid | https://orcid.org/0000-0002-7969-576X | es |
renati.author.dni | 71749702 | - |
renati.advisor.dni | 06112951 | - |
renati.type | http://purl.org/pe-repo/renati/type#tesis | es |
renati.level | http://purl.org/pe-repo/renati/nivel#tituloProfesional | es |
renati.discipline | 711046 | - |
renati.juror | Ventosilla Zevallos, Moisés Odavio | - |
renati.juror | Flores Tinoco, Moisés Ariste | - |
dc.publisher.country | PE | es |
dc.subject.ocde | http://purl.org/pe-repo/ocde/ford#2.02.01 | es |
Aparece en las colecciones: | Ingeniería Electrica |
Ficheros en este ítem:
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
pastor_ej.pdf | 13,62 MB | Adobe PDF | Visualizar/Abrir | |
informe_de_similitud.pdf | 815,97 kB | Adobe PDF | Visualizar/Abrir | |
pastor_ej(acta).pdf | 440,75 kB | Adobe PDF | Visualizar/Abrir | |
carta_de_autorización.pdf | 790,98 kB | Adobe PDF | Visualizar/Abrir |
Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons
Indexado por: