dc.description.abstractEl presente trabajo lleva como título: “Implementación de un chiller para mejorar la eficiencia y carga térmica en condiciones de baja demanda de un sistema de aire acondicionado en un edificio corporativo”. El propósito de esta investigación es determinar el tipo de chiller adecuado para el acondicionamiento del sistema del aire acondicionado del edificio corporativo Alto Caral en temporadas de baja temperatura y/o baja demanda de carga, pero en general puede ser aplicado como metodología para la selección de chillers en otros edificios que tienen la misma problemática ya que se basa en estándares internacionales. El tipo de investigación es cuantitativo, y el método para desarrollar la investigación es deductivo directo, el cual es la implementación de un chiller y que debe influir en el enfriamiento adecuado del sistema de aire acondicionado del edificio, se podrá contrastar dichos resultados después de la evaluación energética y rendimiento del equipo chiller. Resultados: una vez realizado el levantamiento de datos, se comprobó que el chiller seleccionado cumple el requerimiento de carga térmica mínima de 40 toneladas de refrigeración de carga sostenida corrigiendo el problema de cortociclaje y migración de aceite, se redujo el consumo eléctrico en temporadas de baja temperatura y/o baja demanda de carga llegando a valores de reducción del 52.4 % en el consumo eléctrico y se obtuvo valores de COP mayores a 6 (de acuerdo a normas ANSI/ASHRAE/IES Standard 90.1) . Conclusión: se seleccionó adecuadamente un Chiller de agua helada usando una metodología para la selección del Chiller de 200 toneladas de refrigeración y se validó su instalación en campo con las modificaciones respectiva adecuándose al sistema actualmente instalado.es
dc.description.abstractThe title of this work is: “Implementation of a chiller to improve efficiency and thermal load in low demand conditions of an air conditioning system in a corporate building”. The purpose of this research is to determine the type of chiller suitable for conditioning the air conditioning system of the Alto Caral corporate building in low temperature and/or low load demand seasons, but in general it can be applied as a methodology for the selection of chillers in other buildings that have the same problem since it is based on international standards. The type of research is quantitative, and the method to develop the research is direct deductive, which is the implementation of a chiller and which should influence the adequate cooling of the building's air conditioning system. These results can be contrasted after the energy evaluation and performance of the chiller equipment. Results: Once the data collection was carried out, it was verified that the selected chiller meets the minimum thermal load requirement of 40 tons of sustained load refrigeration, correcting the short-cycle and oil migration problem, the electrical consumption was reduced during low temperature and/or low load demand seasons, reaching reduction values of 52.4% in electrical consumption, and COP values greater than 6 were obtained (according to ANSI/ASHRAE/IES Standard 90.1). Conclusion: A chilled water chiller was appropriately selected using a methodology for the selection of the 200-ton refrigeration chiller and its installation in the field was validated with the respective modifications, adapting to the currently installed system.en
dc.description.uriTrabajo de suficiencia profesionales
dc.formatapplication/pdfes
dc.language.isospaes
dc.publisherUniversidad Nacional de Ingenieríaes
dc.rightsinfo:eu-repo/semantics/openAccesses
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/es
dc.sourceUniversidad Nacional de Ingenieríaes
dc.sourceRepositorio Institucional - UNIes
dc.subjectAire acondicionadoes
dc.subjectEdificio corporativoes
dc.subjectChilleres
dc.subjectCarga térmicaes
dc.subjectConsumo eléctricoes
dc.titleImplementación de un chiller para mejorar la eficiencia y carga térmica en condiciones de baja demanda de un sistema de aire acondicionado en un edificio corporativoes
dc.typeinfo:eu-repo/semantics/bachelorThesises
thesis.degree.nameIngeniero Mecánicoes
thesis.degree.grantorUniversidad Nacional de Ingeniería. Facultad de Ingeniería Mecánicaes
thesis.degree.levelTítulo Profesionales
thesis.degree.disciplineIngeniería Mecánicaes
thesis.degree.programIngenieríaes
renati.advisor.orcidhttps://orcid.org/0000-0003-1494-9690es
renati.author.dni09706628-
renati.advisor.dni07160486-
renati.typehttps://purl.org/pe-repo/renati/type#trabajoDeSuficienciaProfesionales
renati.levelhttps://purl.org/pe-repo/renati/level#tituloProfesionales
renati.discipline713046-
renati.jurorRavelo Chumioque, José Jaime-
renati.jurorCaballero Torres, Eduardo-
dc.publisher.countryPEes
dc.subject.ocdehttps://purl.org/pe-repo/ocde/ford#2.03.01es
Aparece en las colecciones: Ingeniería Mecánica

Ficheros en este ítem:
Fichero Descripción Tamaño Formato  
rospigliosi_ga.pdf4,91 MBAdobe PDFVisualizar/Abrir
rospigliosi_ga(acta).pdf300,28 kBAdobe PDFVisualizar/Abrir
informe_de_similitud.pdf581,3 kBAdobe PDFVisualizar/Abrir
carta_de_autorización.pdf221,8 kBAdobe PDFVisualizar/Abrir


Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons Creative Commons

Indexado por:
Indexado por Scholar Google LaReferencia Concytec BASE renati ROAR ALICIA RepoLatin UNI