Título : | Modelado del método del lazo conductor para mitigar el campo magnético debajo de líneas eléctricas urbanas |
Autor : | Gonzales San Martin, Pedro Sebastian |
Asesor : | Yanque Montufar, Justo Hermilo |
Palabras clave : | Campos electromagnéticos (CEM);Mitigación;Lazo conductor pasivo;Líneas eléctricas aéreas |
Fecha de publicación : | 2022 |
Editorial : | Universidad Nacional de Ingeniería |
Resumen : | En el presente trabajo se realiza un análisis y modelamiento de un método para el control de la exposición a campos magnéticos producido por líneas eléctricas ya existentes o en planificación que pasan por zonas urbanas y se genera un algoritmo para reducir el campo magnético en casos se superen las normas y recomendaciones adoptadas en el Perú. El método se basa en colocar un lazo conductor debajo en el vano que se desee mitigar y este lazo, mediante el principio de inducción Ley de Faraday y Lenz genere un campo que se oponga al campo generado por la línea.
El cálculo que se realiza en el presente informe considera el efecto de flecha de los conductores debido a su propio peso, mejorando así y dando mayos sustento a los resultados. Además, el método se aplica a diferentes tipos de configuraciones de líneas eléctricas como la bandera, doble bandera, tres bolillos, tipo capa, etc; a fin de encontrar la ubicación ideal a la cual se tendría una mayor mitigación del campo magnético.
El método propuesto se aplica a posibles lugares donde el campo magnético pueda ser alto y se analiza el benefició que otorgará el método. También se realiza un breve análisis económico, mecánico-estructural y eléctrico para estudiar la viabilidad del método del lazo conductor. In the present work, an analysis and modeling of a method for the control of the exposure to magnetic fields produced by existing power lines or in planning that pass through urban areas is carried out and an algorithm is generated to reduce the magnetic field in cases that are exceeded. the norms and recommendations adopted in Peru. The method is based on placing a conductive loop below the opening to be mitigated and this loop, by means of the Faraday and Lenz Law induction principle, generates a field that opposes the field generated by the line. The calculation made in this report considers the deflection effect of the conductors due to their own weight, thus improving and giving greater support to the results. In addition, the method is applied to diverse types of power line configurations such as flag, double flag, three bobbins, layer type, etc; to find the ideal location to which the greatest mitigation of the magnetic field would be obtained. The proposed method is applied to places where the magnetic field may be high and the benefit that the method will provide is analyzed. A brief economic, mechanical-structural, and electrical analysis is also carried out to study the feasibility of the conductive loop method. |
URI : | http://hdl.handle.net/20.500.14076/26617 |
Derechos: | info:eu-repo/semantics/restrictedAccess |
Aparece en las colecciones: | Ingeniería Electrica |
Ficheros en este ítem:
Fichero | Descripción | Tamaño | Formato | |
---|---|---|---|---|
gonzales_sp.pdf | 3,99 MB | Adobe PDF | Visualizar/Abrir | |
gonzales_sp(acta).pdf | 535,84 kB | Adobe PDF | Visualizar/Abrir | |
informe_de_similitud.pdf | 543,26 kB | Adobe PDF | Visualizar/Abrir |
Este ítem está sujeto a una licencia Creative Commons Licencia Creative Commons
Indexado por: