Title: | Análisis del comportamiento de micropilotes inyectados para estabilizar estructuras de la subestación eléctrica Cáclic - Amazonas, cimentadas sobre terrenos problemáticos |
Authors: | Llana Córdova, Joel Ever |
Advisors: | Calderón Cahuana, Diana Lucía |
Keywords: | Micropilotes;Estabilidad estructural;Subestaciones eléctricas |
Issue Date: | 2023 |
Publisher: | Universidad Nacional de Ingeniería |
Abstract: | La presente investigación tiene como finalidad analizar el comportamiento de los micropilotes inyectados sometidos a esfuerzos de flexión y cortante, utilizados como alternativa de cimentación sobre terrenos problemáticos y por tanto mitigar el asentamiento de las estructuras cimentadas de los equipos electromecánicos de la Subestación Eléctrica Cáclic.
La Subestación Eléctrica Cáclic, ubicada en la periferia de la ciudad de Chachapoyas, se construyó sobre un terraplén de relleno controlado constituido por suelos de naturaleza limo-arcillosa con características dispersivas que varían de 54.87 a 85.40% de dispersión, colocado sobre una roca identificada como brecha calcárea en proceso kárstico perteneciente a la Formación lnguilpata, de perforaciones diamantinas realizadas se obtienen muestras recuperadas que varían desde 58. 7 a 88. 7%.
Debido a las intensas lluvias, la falta de control en el drenaje y a la nula protección de las excavaciones, el material fino del terraplén, compuesto por limos, arenas y arcillas con características dispersivas, fueron erosionados por la acción física del agua fluyendo a través de este, provocando la migración y arrastre de material fino debido a un proceso de erosión interna conocido como tubificación, perdiéndose a mayores profundidades por las cavidades conectadas (porosidad secundaria) de la roca brecha calcárea fosilífera en proceso kárstico.
Utilizando micropilotes inyectados, el factor de seguridad se incrementa en 5.30 y 3.30 veces para los equipos, transformador de potencia y reactor, respectivamente, permitiendo de esta manera estabilizar las estructuras. La capacidad admisible de los micropilotes inyectados es de 63.54 ton y 44.67 ton para el trasformador de potencia y reactor, respectivamente. Las deformaciones verticales de los micropilotes del transformador de potencia son de 0.082 cm en la sección X y de 0.096 cm en la sección Y. Las deformaciones verticales de The purpose of this research is to analyze the behavior of injected micropiles subjected to bending and shear stresses, used as a foundation alternative on problematic terrain and therefore mitigate the settlement of the foundation structures of the electromechanical equipment of the Cáclic Electrical Substation. The Cáclic Electric Substation, located on the outskirts of the city of Chachapoyas, was built on a controlled fill embankment made up of silt-clayey soils with dispersive characteristics that vary from 54.87 to 85.40% dispersion, placed on a rock identified as calcareous breccia in karstic process belonging to the lnguilpata Formation, from diamond perforations carried out, recovered samples are obtained that vary from 58. 7 to 88. 7%. Due to the intense rains, the lack of control in the drainage and the null protection of the excavations, the fine material of the embankment. composed of silt. sand and clay with dispersive characteristics, were eroded by the physical action of the water flowing through this, causing the migration and dragging of fine material due to an interna! erosion process known as tubing, being lost at greater depths through the connected cavities (secondary porosity) of the fossiliferous calcareous breccia rock in karstic process. Using injected micropiles, the safety factor is increased by 5.30 and 3.30 times for the equipment, power transformer and reactor, respectively, thus allowing the structures to be stabilized. The permissible capacity of the injected micropiles is 63.54 tons and 44.67 tons for the power transformer and reactor, respectively. The vertical deformations of the micropiles of the power transformer are 0.082 cm in section X and 0.096 cm in section Y. The vertical deformations of the micropiles of the reactor are 0.033 cm in section X and 0.034 cm in section Y. |
URI: | http://hdl.handle.net/20.500.14076/27643 |
Rights: | info:eu-repo/semantics/openAccess |
Appears in Collections: | Ingeniería Civil |
Files in This Item:
File | Description | Size | Format | |
---|---|---|---|---|
llana_cj.pdf | 45,45 MB | Adobe PDF | View/Open | |
llana_cj(acta).pdf | 716,91 kB | Adobe PDF | View/Open | |
carta_de_autorización.pdf | 712,89 kB | Adobe PDF | View/Open | |
informe_de_similitud.pdf | 1,63 MB | Adobe PDF | View/Open |
This item is licensed under a Creative Commons License
Indexado por: