Title: Medición y análisis de los armónicos en el sistema eléctrico de un centro comercial para mejorar la calidad de energía
Authors: Escajadillo Ayquipa, Ronald
Advisors: Alva Dávila, Fortunato
Keywords: Sistema eléctrico;Calidad de energía;Potencia reactiva;Luminarias led
Issue Date: 2025
Publisher: Universidad Nacional de Ingeniería
Abstract: La presente investigación tuvo como objetivo general la medición y análisis de los armónicos presentes en las tiendas Retail de los centros comerciales. Para el desarrollo de la investigación la metodología fue del tipo aplicada, el nivel descriptiva y explicativa, diseño cuantitativo y enfoque experimental, tomando como población y muestra al sistema eléctrico del local comercial Oechsle del Real Plaza Cusco. Para la medición y análisis se utilizó un analizador de redes de marca Fluke modelo 435 II; el procesamiento de la información de los valores registrados se realizó mediante el software Power Log 5.9, los cuales deberán estar dentro de los límites permitidos que manda la norma IEEE 519-2022 y la NTCSE 020-97-EM. Como resultado se observó que las tensiones armónicas THD estaban dentro de lo que manda la norma, es decir menos del 8%; lo que si se visualizo es que las corrientes armónicas alcanzaron un valor máximo del 42%; de igual manera se menciona que se obtuvo un valor de -32KVAR de potencia reactiva capacita, el cual estaría generando perturbaciones al sistema eléctrico.
The present research aimed to measure and analyze the harmonics present in retail stores within shopping centers. For the development of the study, the methodology was applied research, with a descriptive and explanatory level, quantitative design, and experimental approach, taking as the population and sample the electrical system of the Oechsle store at Real Plaza Cusco. For measurement and analysis, a Fluke 435 II power quality analyzer was used; the processing of the recorded data was carried out using Power Log 5.9 software, with the results required to remain within the limits established by the IEEE 519-2022 standard and the NTCSE 020-97-EM regulation. The results showed that the total harmonic distortion (THD) of voltages was within the standard limits, that is, less than 8%. However, it was observed that harmonic currents reached a maximum value of 42%. Likewise, it was noted that a value of -32 kVAR of capacitive reactive power was obtained, which could be causing disturbances to the electrical system.
URI: http://hdl.handle.net/20.500.14076/28997
Rights: info:eu-repo/semantics/openAccess
Appears in Collections:Ingeniería Mecánica y Electrica

Files in This Item:
File Description SizeFormat 
escajadillo_ar.pdf1,66 MBAdobe PDFView/Open
escajadillo_ar(acta).pdf477,3 kBAdobe PDFView/Open
informe_de_similitud.pdf482,25 kBAdobe PDFView/Open
carta_de_autorización.pdf216,99 kBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons

Indexado por:
Indexado por Scholar Google LaReferencia Concytec BASE renati ROAR ALICIA RepoLatin UNI